WP#16 - Quantitative Analysis of Power Distribution Configurations for Data Centers

WP#16 - Quantitative Analysis of Power Distribution Configurations for Data Centers

Please sign in to download this item.

By downloading this content I acknowledge that I will use the content in accordance with The Green Grid's Terms of Use

Document
Product Authors

Power Sub Work Group

This analysis builds on the previously released “Qualitative Analysis of Power Distribution Configurations for Data Centers.” [link to white paper 4] It takes a quantitative look at one aspect of the previous paper – efficiency. This paper studies the end-to-end efficiency of eight simplified, non-redundant data center power distribution configurations. The data shows that a data center with optimized implementations of all of the topologies achieve approximately 25% higher efficiency than a typical data center of 10 years ago, delivering between 85% and 90% end-to-end efficiency over a wide load range. The highest efficiency AC and DC configurations are within 1% to 2% of each other and are only 2% to 3% better than double conversion 480Vac – 208Vac over the majority of the load range. No single configuration provides the highest efficiency at every load.